Sizing a battery pack for commercial and industrial (C&I) energy storage starts with understanding how a facility consumes electricity and when battery power is needed. A battery designed for peak shaving may need high discharge power over a short period, while a system designed for load shifting may need to deliver energy over several hours.
The most reliable approach is to translate the site's load profile into measurable battery requirements. These include discharge power, delivered energy, nominal capacity, charging requirements, and electrical integration constraints. The resulting specification helps project developers, BESS integrators, and procurement teams evaluate standard battery configurations and determine whether a custom battery pack is necessary.
A battery load profile describes the power demand that an energy storage battery is expected to support over time. The analysis usually starts with historical site load data and identifies when, how much, and for how long the battery must charge or discharge.
For a commercial energy storage project, collect the following information:
Fifteen-minute interval data is often suitable for preliminary peak-shaving analysis. However, it may conceal short-duration demand spikes or equipment start-up peaks. Where these affect the required power rating, use higher-resolution measurements or additional equipment-level data.
It is also important to distinguish between the site's load profile and the battery's duty profile. The site load profile shows the facility's electricity demand. The battery duty profile defines the power the battery must deliver or absorb over time to meet the project's operating objectives.
The battery duty profile, rather than the site's total electricity consumption alone, should be used to determine battery power and energy requirements.
Before sizing the battery, identify the primary operating objective. Different applications can produce different power and capacity requirements even when they use the same site load data.
| Application | What to Analyze | Key Battery Requirement |
|---|---|---|
| Peak shaving | Demand exceeding the target grid-import limit and the duration of each peak. | Peak discharge power and total energy required during the peak event. |
| Load shifting | Energy required during high-cost periods and available charging windows during lower-cost periods. | Usable energy, discharge duration, and recharge capability. |
| Solar self-consumption | Periods when PV generation exceeds site demand and periods when demand exceeds generation. | Surplus solar energy, charging power, and later discharge requirements. |
| Grid-constrained operation | Demand that exceeds the available grid connection capacity. | Power deficit, duration, and opportunities to recharge before the next event. |
For projects combining PV and battery storage, charging requirements should be evaluated alongside discharge requirements. The battery must have enough available capacity to absorb surplus generation and enough charging power to use the available solar window.
For related specification considerations, see our guide to specifying a custom battery for a solar PV energy storage system.
Battery sizing requires separate power and energy calculations. Power, measured in kilowatts (kW), indicates how much electricity must be delivered at a given moment. Energy, measured in kilowatt-hours (kWh), indicates how much electricity must be delivered over a period of time.
For peak shaving, define the target grid-import limit first. For each time interval, calculate the portion of site demand that exceeds this target.
Where:
The highest calculated value across the analyzed intervals gives the preliminary maximum interval-average discharge power:
This result is not necessarily the maximum instantaneous power required. Short-duration peaks, motor starts, and other transient loads may require a higher power rating and should be assessed separately.
For load-shifting and solar self-consumption applications, calculate the battery's charging and discharging profiles according to the intended operating schedule. The peak-shaving formula above is an example for a specific operating objective, not a universal formula for every energy storage application.
Calculate the energy required during each interval by multiplying the battery's discharge power by the interval duration. Add the interval results to determine the total energy required for the event.
Where:
For example, if a battery delivers an average of 55 kW for 15 minutes:
When the load varies, calculate each interval separately. Multiplying the peak power by the entire event duration can produce an inaccurate energy estimate if the battery is not required to operate at peak power throughout the event.
Keep the measurement boundary consistent. Confirm whether site demand is measured on the AC side and whether the battery's rated energy is specified on the DC side. If the required energy is measured at the site AC connection, account for PCS conversion losses and other relevant discharge-path losses when translating it into a battery-side requirement. Do not apply the same losses twice.
The battery's nominal capacity is not the same as the energy that can be delivered to the site. The available energy depends on the permitted state-of-charge (SOC) window and the losses between the battery and the specified delivery point.
A preliminary nominal-capacity estimate is:
Where:
Use supplier-supported performance data and project-specific operating limits. If the supplier's usable-energy rating already accounts for the relevant SOC limits or conversion losses, do not apply those factors again.
Account for end-of-life capacity requirements. If the battery must still deliver the required energy at the specified end of life (EOL), and the quoted capacity does not already account for degradation, a preliminary estimate is:
fEOL is the retained-capacity fraction at the specified end of life. It should be based on the supplier's documented performance and the project's operating conditions. If the energy requirement is already defined as usable energy at EOL, do not apply the retention factor again.
For more detail on the difference between rated capacity and energy available for operation, see Rated Energy vs. Usable Energy in Battery Storage.
Consider a commercial facility that wants to limit grid import to 310 kW during a peak-demand period. The following hypothetical example uses site-load averages recorded over 15-minute intervals. Each timestamp marks the beginning of the interval, and the target remains 310 kW throughout the event.
| Interval Start | Average Site Load (kW) | Required Battery Output (kW) | Energy per Interval (kWh) |
|---|---|---|---|
| Calculated Requirement | 110 kW | 75.00 kWh | |
| 16:00 | 285 | 0 | 0.00 |
| 16:15 | 320 | 10 | 2.50 |
| 16:30 | 365 | 55 | 13.75 |
| 16:45 | 420 | 110 | 27.50 |
| 17:00 | 390 | 80 | 20.00 |
| 17:15 | 350 | 40 | 10.00 |
| 17:30 | 315 | 5 | 1.25 |
| 17:45 | 295 | 0 | 0.00 |
The calculated battery duty profile produces two key results:
The 110 kW result is based on 15-minute average load data. Higher-resolution measurements may reveal additional instantaneous power requirements. The final power rating must also be checked against the battery's discharge limits and the selected PCS rating.
Assume, for illustration, that 90% of nominal energy is available within the permitted SOC window and the applicable discharge-path efficiency is 95%.
This is a preliminary beginning-of-life estimate under the stated assumptions. If the project also requires the same 75 kWh of delivered energy at EOL and the supplier-supported capacity-retention factor is 80%, the estimate becomes:
The 80% retention value is illustrative, not a universal design assumption. Use documented supplier data for the required service life and operating conditions.
These calculations establish a preliminary capacity range, not a complete system design. Before selecting a battery, confirm the energy-rating boundary, SOC limits, conversion losses, operating temperature, and end-of-life assumptions used by the supplier.
A load-profile calculation identifies the preliminary power and energy requirements. The selected battery configuration must also satisfy the electrical, thermal, lifecycle, and integration conditions of the commercial energy storage project.
Check that the battery can sustain the required discharge power for the full duration of each event. Confirm continuous and peak discharge ratings, operating voltage, allowable current, and the limits of the battery management system (BMS).
For a preliminary DC-side current estimate:
Here, IDC is current in amperes, PDC is DC power in watts, and VDC is DC voltage in volts. Use values from the same electrical side. This is a preliminary estimate because actual current varies with operating voltage and system losses.
For repeated peak shaving, load shifting, or solar self-consumption, determine how much energy must be restored before the next discharge period. Compare the required recharge energy with the available charging window and confirm that the charging power is supported by the battery and the wider system.
For PV-coupled projects, also consider whether surplus generation is sufficient to recharge the battery when required. A battery with adequate nominal capacity may still fail to meet the operating objective if the available charging power or charging window is insufficient.
Verify that the proposed battery configuration is suitable for the installation environment and operating temperature range. Review the following requirements before finalizing the battery specification:
These checks help distinguish a battery that meets the calculated kWh requirement from one that is suitable for the actual commercial energy storage application.
A custom battery pack may be appropriate when standard configurations cannot meet the project's documented electrical, mechanical, control, or operating requirements. The load-profile analysis helps identify whether the remaining gap concerns power, energy, discharge duration, voltage, or integration.
Before commissioning a custom design, compare the complete battery duty profile with available standard configurations. Consider whether the requirement can be met through a different standard battery configuration or a suitable adjustment to the operating schedule or system design.
A custom pack may be worth evaluating when:
For projects with these requirements, explore custom battery pack design and smart integration. The feasibility of a custom solution depends on the detailed electrical requirements, system interfaces, safety requirements, and validation scope.
A useful request for quotation (RFQ) translates the calculated battery duty profile into requirements that suppliers can assess consistently. Instead of specifying only a nominal capacity in kWh, provide the load data, operating schedule, measurement boundaries, and integration constraints.
Providing these details allows suppliers to assess whether a standard battery configuration is suitable or whether a custom pack should be evaluated. It also makes technical and commercial quotations easier to compare on a consistent basis.
A battery load profile provides the foundation for converting commercial site demand into practical energy storage requirements. Define the battery's operating objective, calculate discharge power for each interval, sum the energy required over the operating period, and estimate nominal capacity using clearly defined SOC, efficiency, and lifecycle assumptions.
Then validate the results against charging capability, voltage and current limits, operating temperature, protection, and system interfaces. This approach helps commercial energy storage developers, integrators, and procurement teams assess battery configurations based on actual project requirements rather than nominal capacity alone.
If you are evaluating a custom battery pack for a commercial energy storage project, prepare the load profile and preliminary electrical requirements before starting a technical discussion with a supplier. Clear requirements provide a stronger basis for feasibility assessment, integration planning, and RFQ comparison.
Turn your site load profile into a practical battery specification. Share your target discharge power, required energy, operating schedule, voltage range, and system integration requirements with ACE Battery.
Our team can help assess battery pack feasibility and discuss suitable customization options based on your project's technical requirements.